How to use it
- Pick a circuit type and enter the electrical input power. Select W or kW to match your value.
- Enter the voltage. For AC, enter the power factor from 0 to 1, excluding 0. For balanced three-phase AC, use total power and line-to-line RMS voltage.
- Press Calculate to see the current and the formula with your numbers. For AC, the result is RMS current.
Questions and answers
Why do I need voltage to convert watts to amps?
Watts describe power and amps describe current. In DC, the same 60 W draws 5 A at 12 V or 2.5 A at 24 V.
Can I enter apparent power in VA?
Use active input power in W or kW. If you have apparent power, multiply VA by the power factor first to get watts.
What does the current result represent?
It is the steady-state current for the inputs and circuit type you entered. The three-phase result is current in each line of a balanced load.
Common questions and fixes
How do you add up the current of several 12 V devices?
Add the input power of the devices running together on the same 12 V DC supply, then divide by 12 V. A 36 W light and an 18 W fan draw 4.5 A together at that voltage. You can also convert each load separately and add their currents.
Step by step
- Verify that each watt figure is the electrical input power on the same DC supply.
- Add the watts of the devices that will be running at the same time.
- Select DC and enter the total watts and the supply voltage. Compare with your per-device results if needed.
How does power factor change current at the same watts?
With the same voltage and active input watts, a lower power factor means higher current. At 1,200 W and 120 V single-phase, the current is 10 A at PF 1 or 12.5 A at PF 0.8. Divide watts by voltage times power factor.
Step by step
- Select single-phase AC and enter 1,200 W and 120 V RMS.
- Enter 1 for the power factor and calculate the baseline.
- Change it to 0.8, then 0.5, without changing the watts or voltage.
Which voltage goes into a three-phase amps calculation?
Enter the RMS voltage measured between two lines. In a 480Y/277 V example, use 480 V with total active power. At 12 kW and a power factor of 0.8, the balanced current is about 18.04 A per line.
Step by step
- Check which of the given voltages is between two lines.
- Select balanced three-phase AC, enter the total 12 kW, then enter 480 V RMS and PF 0.8.
- Compare the result with 12,000 ÷ (√3 × 480 × 0.8). Keep that current per line.